System
|
|
|
|
|
|
|
|
|
|
|
|
PWR: Power Input plugged and On (Green) RDY: System startup ready (Red)
|
|
Network Interface
|
|
IEEE 802.3 10Base-T, IEEE 802.3u 100Base-TX
|
|
|
|
|
Built-in 1.5 KV magnetic isolation protection
|
|
|
Upper (LAN Activity): Orange On & Blinking Lower(10M/100M): 10M (Green Off) /100M(Green ON)
|
|
Thermocouple / Analog Input
|
|
|
|
|
|
Thermocouple (T/C), mV, V, mA
|
|
|
Voltage: ±2.5V,±1V, ±500mV, ±100mV, ±50mV, ±15mV Current: ±20mA with external 125Ohm resistor
|
|
|
K/J/N/C/E/B/T/R/S type T/C
Type
|
Range
|
K
|
-100°C ~ 1000°C
|
J
|
-100°C ~ 900°C
|
N
|
-270°C ~ 1300°C
|
C
|
10°C ~ 2310°C
|
E
|
-240°C ~ 2310°C
|
B
|
0°C ~ 1800°C
|
T
|
-270°C ~ 400°C
|
R
|
-50°C ~ 1530°C
|
S
|
-50°C ~ 1700°C
|
|
|
T/C Open Circuit Detection
|
|
|
|
|
|
|
|
|
|
|
|
|
Feature
|
|
IP, TCP, UDP, SNMP, HTTP, BOOTP, DHCP, Modbus/TCP, OPC Server
|
|
|
Windows Utility, Web, SNMP, DHCP Client, BootP for firmware update
|
|
|
one-to-one, one-to-many, many-to-one, and many-to-many communication
|
|
|
|
|
OPC Server for Modbus/TCP
|
|
|
MIB-II: System, SNMP Trap and Private MIB
|
|
|
|
|
High-/Low- Voltage/ Current alarms
|
|
|
Conditions of the AI and temperature values, Actions include the trap
|
|
Power Requirements
|
|
external unregulated +24V (18-32V)
|
|
|
|
Mechanical
|
|
120 (H) x 55 (W) x 75 (D) mm
|
|
|
|
|
|
Environmental
|
|
|
|
|
|
|
|
|
|
|